Looking for prices?
Sign in Become a Customer


3385510

Rittal TopTherm SK Series 1-Phase Cooling Unit, 115 VAC, 14.2/15.4 A, 50/60 Hz, NEMA 12/IP34/IP54 Enclosure, 4811/5152/6824/7301 Btu


3385510

Rittal TopThermâ„¢ Cooling Unit, 1-Phase, Series: SK Series, 115 VAC, 14.2/15.4 A, 1.41/1.51/2/2.14 kW Power, 50/60 Hz Frequency, 4811/5152/6824/7301 Btu Capacity, NEMA 12/IP34/IP54 Enclosure, e-Comfort Controller Control, Plug-In Terminal Strip Connection, 10 to 55 deg C, Roof Mounting, Sheet Steel, Light Gray, 16 in H x 24 in W x 19 in D Dimensions

Description
Energy-efficient Blue e roof-mounted cooling units with integral e-Comfort controller, RiNano coating on the condenser and electric condensate evaporation as standard.
Benefits
May be linked to the IoT interface via the Blue e IoT adaptor
Material
Carbon Steel
Colour
Light Gray
IP Rating
External Circuit: IP34, Internal Circuit: IP54
Supply Includes
Nano-coated condenser Integral electric condensate evaporation wired ready for connection (plug-in terminal strip), drilling template fasteners
Note
Due to its low noise level, the roof-mounted cooling unit 3273.500 is also suitable for use in office applications.
Variant
Roof-Mounted
Total Cooling Output to DIN EN 14511
L 35 L 35 @ 50 Hz: 2 kW (6824 BTU) L 35 L 35 @ 60 Hz: 2.14 kW (7301 BTU) L 35 L 50 @ 50 Hz: 1.41 kW (4811 BTU) L 35 L 50 @ 60 Hz: 1.51 kW (5152 BTU)
Air Throughput (Unimpeded Air Flow)
External circuit: 1760 m sq/h (1035.9 cfm) Internal circuit: 470 m sq/h (276.6 cfm)
Rated Operating Voltage
115V, 1~, 50/60 Hz
Dimensions
16 in H x 24 in W x 19 in D
Temperature Control
e-Comfort Controller (factory setting 35 deg C)
Temperature Range
Operating Temperature: 10 to 55 deg C, Setting Range: 20 to 50 deg C
Refrigerant/Cooling Medium
900g of R134A
Type of Electrical Connection
Plug-in Terminal Strip
Duty Cycle
100%
Rated Power Pel
L 35 L 35 at 50 Hz: 0.95 kW L 35 L 35 at 60 Hz: 1.17 kW L 35 L 50 at 50 Hz: 1.07 kW L 35 L 50 at 60 Hz: 1.24 kW
Maximum Rated Current
13.3 A at 50 Hz, 13.5 A at 60 Hz
Start-up Current (Max.)
42.2 A at 50 Hz, 31.1 A at 60 Hz
Pre-Fuse
Transformer Circuit-Breaker: 14/20 A
Packaging Unit
1 pc
Gross Weight
48 kg (105.8 lb)
Add to Cart