- Input Voltage
- 475 to 600 VAC
- Maximum Input Power
- 6
- Input AC Line Frequency
- 50/60 Hz (50 will increase all delay timers by 20%)
- Output Form
- Form C
- Output Load Rating (VA)
- Pilot Duty: 480 VA @ 240 VAC B300; General Purpose: 10 A @ 240 VAC
- Restart Delay Range
- 1 to 500 s Adjustable
- Trip Delay Range
- Under/Over and Unbalance Voltage: 1 to 30 s adjustable; single-phase faults (> 25% UB): 1 s fixed
- Trip Point Accuracy
- 1%
- Overvoltage Trip Voltage (%)
- 110%
- Overvoltage Reset Voltage (%)
- 107%
- Undervoltage Trip Voltage
- 90%
- Undervoltage Reset Voltage (%)
- 93%
- Voltage Unbalance Trip Point
- 2 to 8% Adjustable
- Voltage Unbalance Reset
- Trip setting minus 1% (5 to 8%), Trip setting minute 0.5% (2 to 4%)
- IP Rating
- IP20, NEMA 1
- Termination Type
- Torque: 6 in-lbs; Wire: Stranded or Solid 12-20 AWG one per Terminal
- Mounting Options
- 35 mm DIN rail or Surface Mount (#6 or #8 Screws)
- Operating Temperature
- -20 to 70 deg C (-4 to 158 deg F)
- Storage Temperature
- -40 to 80 deg C (-40 to 176 deg F)
- Max Op. Relative Humidity Non-Condensing (%)
- 10 - 95%
- Dimensions
- 3.5 H x 2.08 W x 2.35 D in. (88.9 x 52.9 x 59.7 mm)